Interconnection Engineering & Smart Inverter Codes

Utility Grid Codes & Interconnection Standards

Technical rules for distributed energy resources: Low-Voltage Ride-Through (LVRT), autonomous frequency-watt droop, Volt-VAR feeder stabilization, anti-islanding, and utility communications.

Low Voltage (LV < 1kV)IEEE 1547-2018 & UL 1741-SB

North American Interconnection (IEEE 1547-2018 / CA Rule 21)

Territory: United States (CAISO, ERCOT, PJM, NYISO)

Browse Compliant Inverters
Fault Ride-Through (LVRT / HVRT)

Remain connected down to 0.50 p.u. voltage for up to 10.0 seconds (Mandatory Trip at < 0.45 p.u. within 0.16s)

Frequency Operating Window & Droop

Continuous operation between 58.8 Hz and 61.2 Hz; Mandatory trip at < 56.5 Hz or > 62.0 Hz

Anti-Islanding Disconnection Time

Must disconnect within 2.0 seconds upon loss of grid reference

Autonomous Reactive Power (VAR) Modes

  • Volt-VAR (autonomous curve)
  • Constant Power Factor (0.90 leading/lagging)
  • Volt-Watt curtailment

Mandatory Features & Telemetry

  • Autonomous Voltage Support during distribution voltage sag
  • Dynamic reactive current injection during balanced and unbalanced faults
  • Remote curtailment and telemetry capability for utility dispatch
Protocol: IEEE 2030.5 (SEP 2.0) via SunSpec CSIP or DNP3